RC Trms 3ph Hero Unit
RCT Options BNC Splitter Generic
RC Trms 3ph Hero Unit 3
RCT 3ph Cables

Product Synopsis

A summary and synopsis of information for the RCTrms-3ph.

RCTrms-3ph

Thin, flexible, clip-around, ac current sensor with true rms output

The RCTrms-3ph is a three channel current sensor for permanent installation.

The RCTrms-3ph can be specified with either a 4-20mA or 0-5V industry standard output making it ideal for process control, status alarms or system monitoring purposes.

Simple to install and easy to retrofit, the Rogowski (sense) coil is thin, lightweight, flexible, and clip-around. The electronic enclosure houses the integrator and signal conditioner to provide an accurate, true rms measurement of the AC current.

RCTrms-3ph current probes offer:

  • Meassure AC current only
  • Three channels
  • 100Arms to 50kArms
  • True RMS measurement
  • 4-20mA True RMS output

The RCTrms-3ph is typically used with SCADA systems, PLCs, data loggers and protection equipment.

RCTrms-3ph Features

  • Traceable calibration (certificate included)
  • Non-magnetic materials mean excellent linearity <0.2% reading
  • Fully isolated measurement
    • Isolated power supply 2kVdc
    • 2kV peak insulated coil
  • Small DIN rail enclosure
  • 3 Rogowski coils, connected to a small DIN rail enclosure providing 3 outputs

Standards and Approvals

  • CE marked
  • Complies with EMC EN61326-1
  • Complies with IEC 61010-1; IEC 61010-2-032
  • PEM Ltd is certified to the ISO9001:2015 standard

PEM are committed to delivering the highest level of quality to our customers, read more about how we strive to achieve this in our Quality Standards and Compliance sections.

nav-ending

Key Features

Highlights of the RCTrms-3ph, main functionalities and unique selling points.
  • Easy to retro-fit

    Lightweight, thin, flexible, clip-around coil for permanent installation.

  • Simple to install

    Exceptionally easy to install and retro-fit into existing plant.

  • Optimal for limited space

    Ideal for applications with limited space for installation and particularly where existing monitoring equipment is installed.

  • Control and monitoring

    Ideal for process control, status alarming or system monitoring in a wide variety of applications, from arc furnaces to power distribution.

  • Non-intrusive

    The device draws no power from the primary circuit.

  • Intrinsically safe

    No danger of open circuit secondaries.

  • Custom cable length

    Longer cables than the standard 1m and 2.5m are available on request.

  • Custom coil length

    Coil lengths longer than the standard 300mm, 500mm, 700mm and 1000mm are available on request.

  • Bespoke options

    Choose from a range of standard options or create a custom design.

nav-ending

Performance

Electrical performance metrics for the RCTrms-3ph.

Technical Specifications

All models

Rated current (rms)
100A, 250A, 500A, 800A, 1000A, 1600A, 2000A, 2500A, 3000A, 4000A, 5000A, 8000A, 10000A, 16000A, 20000A, 25000A, 30000A, 40000A, 50000A
Rated output (Full scale FS)

4 to 20mA -or- 0 to 5Vdc

Output limit

150% FS (28mA dc) -or- 150% FS (7.5V dc)

Supply voltage (Wide input)

12Vdc (-10%) to 24Vdc (+20%) Max.

Input power

2.1W (at rated output)

Operating temperature range

–5°C to +65°C (Integrator electronics)
–20°C to +80°C (Coil and cable)

Bandwidth(-3dB)

2Hz to 100kHz

Response time (10-90%)

1000ms

Accuracy (typ.)

±1.0% of reading (0-5V)
±1.5% of reading (4-20mA)
(10% to 150% FS, 25°C)

Output load

<300Ω for 4 -20mA output
>1kΩ for 0-5V output

Coil length

300mm, 500mm, 700mm or 1000mm
(Longer coils are available on request).

Cable length

1m or 2.5m
(Longer cables are available on request).

Dimensions

Full product dimensions and line drawings for all options and components.

RCTi-3ph / RCTrms-3ph Dimensions

RCTi-3ph / RCTrms-3ph Dimensions

RCT Standard Coil Length Options

300mm
500mm
700mm
1000mm
Longer on request. (Please see our options section).

RCT Standard Cable Length Options

1m and 2.5m
Longer on request. (Please see our options section).

RCTi-3ph / RCTrms-3ph Dimensions (BNC Option)

RCTi-3ph / RCTrms-3ph Dimensions (BNC Option)

BNC Option

Isolated BNC to BNC cable split option. BNC to BNC disconnect to allow easy installation of RCT. Plastic touch proof connection for safety.

RCT Standard Coil Length Options

300mm
500mm
700mm
1000mm
Longer on request. (Please see our options section).

RCT Standard Cable Length Options

1m and 2.5m
Longer on request. (Please see our options section).
nav-ending

What is included?

We also offer a range of additional options for each RCT product. Choose from coil and cable lengths, IPX8 Coils and BNC Splitters. 

  • CE marked
  • Complies with EMC EN61326-1
  • Complies with IEC 61010-1; IEC 61010-2-032
  • PEM Ltd is certified to the ISO9001:2015 standard

PEM are committed to delivering the highest level of quality to our customers, read more about how we strive to achieve this in our Quality Standards and Compliance sections.

 

  • RCT Rogowski Coil

    Rogowski Coil

    A thin, flexible, lightweight, clip-around (sensing) coil.
    (Custom Sizes Available)

  • RCT Options BNC Connecting Cable

    A Connecting Cable

    A cable to connect the Rogowski coil to the electronics. (BNC Option Shown).
    (Custom cable lengths available on request)

  • RC Ti 3ph Din Rail Mount

    Din Rail Mount Enclosure

    Integrator and signal conditioning electronics housed on a DIN rail mounting enclosure.

  • Calibration certificate 3

    Calibration Certificate

    Every unit is supplied with a fully traceable calibration certificate.

RC Trms 3ph Hero Unit 2
RCT 3ph Cables
RCT Options BNC Splitter Generic
RCT IPX8 Rated Rogowski Coil

Customise & Options

If your requirement is outside that listed on our website please contact us to discuss your requirements and application.

  • RCT Options Longer Rogowski Coils

    Longer Coils

    Longer Rogowski coils are available up to 5000mm.
    (Custom lengths available on request)

  • RCT Options Longer BNC Connecting Cable

    Longer Cables

    Longer cables are available up to 50m.
    (Custom lengths available on request)

  • RCT Options BNC Splitter Generic

    BNC Cable Split

    Isolated BNC to BNC cable split option. BNC to BNC disconnect to allow easy installation of RCT. Plastic touch proof connection for safety.

  • RCT IPX8 Rated Rogowski Coil

    IPX8 Rated Rogowski Coil

    Weather proofed coil and cable. A flexible current probe based on Rogowski principle, suitable for measurement in combination with portable devices.

Get a Quote

Build your RCT product options and complete our online quotation form.

Custom Design

We can provide custom designs for one off applications or volume manufacture.

Downloads

RCTrms-3ph downloads for data-sheets, technical notes, CAD files and more.

For more information and documents please see our full technical resources area.

Technical Resources

Browse our extensive resources of technical information, insights and test data.

Get a Quote

Build your RCT product options and complete our online quotation form.

Applications

The RCTrms-3ph can be used across a wide range of applications.

For more information on possible and suitable applications please review the applications below and click each one for further information.

  • Female facility operator controls workshop production line uses computer with screens showing complex ui of machine operation processes controllers machinery blueprints 1936528471
    Process Control
  • Worker with notebook large turbine on background
    50/60Hz Leakage and Bearing Currents
  • High voltage electric pylon
    High Voltage DC (HVDC) Applications
  • Panoramic view of wind farm or wind park with high wind turbines for generation electricity
    Power Grids and Renewable Energy
  • An electrician is on a light pole to maintain a high voltage line on a dangerous electric pole adb 372606618
    Power Grids and Utilities
  • Electroarc furnace at metallurgical plant
    Arc Furnaces
  • Engineer under checking the industry cooling tower air conditioner
    Large AC Currents

Quality Standards

We are committed to delivering the highest standards of excellence to customers.

Compliance

We prioritise compliance with industry standards ensuring all products are safe.

Your web browser is out of date.

Update your browser for better security, speed and to get the best experience on this website.

Update your browser